Appendix
A.8 Settings
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
411
7255
bef.4.Cy:50N-3
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 4. Cycle: 50N-3
8101
MEASURE. SUPERV
Measurem.Superv
OFF
ON
ON
Measurement Supervision
8104
BALANCE I LIMIT
Measurem.Superv
1A
0.10 .. 1.00 A
0.50 A
Current Threshold for Balance
Monitoring
5A
0.50 .. 5.00 A
2.50 A
8105
BAL. FACTOR I
Measurem.Superv
0.10 .. 0.90
0.50
Balance Factor for Current
Monitor
8106
Σ
I THRESHOLD
Measurem.Superv
1A
0.05 .. 2.00 A;
∞
0.10 A
Summated Current Monitoring
Threshold
5A
0.25 .. 10.00 A;
∞
0.50 A
8107
Σ
I FACTOR
Measurem.Superv
0.00 .. 0.95
0.10
Summated Current Monitoring
Factor
8109
FAST
Σ
i MONIT
Measurem.Superv
OFF
ON
ON
Fast Summated Current Monitor-
ing
8201
FCT 74TC
74TC TripCirc.
ON
OFF
ON
74TC TRIP Circuit Supervision
8202
Alarm Delay
74TC TripCirc.
1 .. 30 sec
2 sec
Delay Time for alarm
8301
DMD Interval
Demand meter
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub
Demand Calculation Intervals
8302
DMD Sync.Time
Demand meter
On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour
Demand Synchronization Time
8311
MinMax cycRESET
Min/Max meter
NO
YES
YES
Automatic Cyclic Reset Function
8312
MiMa RESET TIME
Min/Max meter
0 .. 1439 min
0 min
MinMax Reset Timer
8313
MiMa RESETCYCLE
Min/Max meter
1 .. 365 Days
7 Days
MinMax Reset Cycle Period
8314
MinMaxRES.START
Min/Max meter
1 .. 365 Days
1 Days
MinMax Start Reset Cycle in
8315
MeterResolution
Energy
Standard
Factor 10
Factor 100
Standard
Meter resolution
9011A
RTD 1 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Pt 100
Ω
RTD 1: Type
9012A
RTD 1 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Oil
RTD 1: Location
9013
RTD 1 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 1: Temperature Stage 1
Pickup
9014
RTD 1 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 1: Temperature Stage 1
Pickup
9015
RTD 1 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 1: Temperature Stage 2
Pickup
9016
RTD 1 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 1: Temperature Stage 2
Pickup
9021A
RTD 2 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 2: Type
9022A
RTD 2 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 2: Location
9023
RTD 2 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 2: Temperature Stage 1
Pickup
9024
RTD 2 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 2: Temperature Stage 1
Pickup
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments