Functions
2.7 Thermal Overload Protection 49
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
133
2.7.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
2.7.4
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
4201
FCT 49
OFF
ON
Alarm Only
OFF
49 Thermal overload pro-
tection
4202
49 K-FACTOR
0.10 .. 4.00
1.10
49 K-Factor
4203
TIME CONSTANT
1.0 .. 999.9 min
100.0 min
Time Constant
4204
49
Θ
ALARM
50 .. 100 %
90 %
49 Thermal Alarm Stage
4205
I ALARM
1A
0.10 .. 4.00 A
1.00 A
Current Overload Alarm
Setpoint
5A
0.50 .. 20.00 A
5.00 A
4207A
K
τ
-FACTOR
1.0 .. 10.0
1.0
Kt-FACTOR when motor
stops
4208A
T EMERGENCY
10 .. 15000 sec
100 sec
Emergency time
4209
49 TEMP. RISE I
40 .. 200 °C
100 °C
49 Temperature rise at
rated sec. curr.
4210
49 TEMP. RISE I
104 .. 392 °F
212 °F
49 Temperature rise at
rated sec. curr.
No.
Information
Type of In-
formation
Comments
1503
>BLOCK 49 O/L
SP
>BLOCK 49 Overload Protection
1507
>EmergencyStart
SP
>Emergency start of motors
1511
49 O / L OFF
OUT
49 Overload Protection is OFF
1512
49 O/L BLOCK
OUT
49 Overload Protection is BLOCKED
1513
49 O/L ACTIVE
OUT
49 Overload Protection is ACTIVE
1515
49 O/L I Alarm
OUT
49 Overload Current Alarm (I alarm)
1516
49 O/L
Θ
Alarm
OUT
49 Overload Alarm! Near Thermal Trip
1517
49 Winding O/L
OUT
49 Winding Overload
1521
49 Th O/L TRIP
OUT
49 Thermal Overload TRIP
1580
>RES 49 Image
SP
>49 Reset of Thermal Overload Image
1581
49 Image res.
OUT
49 Thermal Overload Image reset