T START MAX
48/66 Motorprot
1 .. 320 sec
10 sec
Maximum Permissible Starting
Time
4304
T Equal
48/66 Motorprot
0.0 .. 320.0 min
1.0 min
Temperature Equalizaton Time
4305
I MOTOR NOMINAL
48/66 Motorprot
1A
0.20 .. 1.20 A
1.00 A
Rated Motor Current
5A
1.00 .. 6.00 A
5.00 A
4306
MAX.WARM STARTS
48/66 Motorprot
1 .. 4
2
Maximum Number of Warm
Starts
4307
#COLD-#WARM
48/66 Motorprot
1 .. 2
1
Number of Cold Starts - Warm
Starts
4308
K
τ
at STOP
48/66 Motorprot
0.2 .. 100.0
5.0
Extension of Time Constant at
Stop
4309
K
τ
at RUNNING
48/66 Motorprot
0.2 .. 100.0
2.0
Extension of Time Constant at
Running
4310
T MIN. INHIBIT
48/66 Motorprot
0.2 .. 120.0 min
6.0 min
Minimum Restart Inhibit Time
4311
ROTOR OVERLOAD
48/66 Motorprot
ON
OFF
Alarm Only
ON
Rotor Overload Protection
4401
Load Jam Prot.
48/66 Motorprot
OFF
ON
Alarm Only
OFF
Load Jam Protection
4402
Load Jam I>
48/66 Motorprot
1A
0.50 .. 12.00 A
2.00 A
Load Jam Tripping Threshold
5A
2.50 .. 60.00 A
10.00 A
4403
TRIP DELAY
48/66 Motorprot
0.00 .. 600.00 sec
1.00 sec
Load Jam Trip Delay
4404
I Alarm
48/66 Motorprot
1A
0.50 .. 12.00 A
1.80 A
Load Jam Alarm Threshold
5A
2.50 .. 60.00 A
9.00 A
4405
ALARM DELAY
48/66 Motorprot
0.00 .. 600.00 sec
1.00 sec
Load Jam Alarm Delay
4406
T Start Blk.
48/66 Motorprot
0.00 .. 600.00 sec
10.00 sec
Load Jam Blocking after motor
start
7001
FCT 50BF
50BF BkrFailure
OFF
ON
OFF
50BF Breaker Failure Protection
7004
Chk BRK CONTACT
50BF BkrFailure
OFF
ON
OFF
Check Breaker contacts
7005
TRIP-Timer
50BF BkrFailure
0.06 .. 60.00 sec;
∞
0.25 sec
TRIP-Timer
7006
50BF PICKUP
50BF BkrFailure
1A
0.05 .. 20.00 A
0.10 A
50BF Pickup current threshold
5A
0.25 .. 100.00 A
0.50 A
7007
50BF PICKUP IE>
50BF BkrFailure
1A
0.05 .. 20.00 A
0.10 A
50BF Pickup earth current
threshold
5A
0.25 .. 100.00 A
0.50 A
7101
FCT 79
79M Auto Recl.
OFF
ON
OFF
79 Auto-Reclose Function
7103
BLOCK MC Dur.
79M Auto Recl.
0.50 .. 320.00 sec; 0
1.00 sec
AR blocking duration after
manual close
7105
TIME RESTRAINT
79M Auto Recl.
0.50 .. 320.00 sec
3.00 sec
79 Auto Reclosing reset time
7108
SAFETY 79 ready
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Safety Time until 79 is ready
7113
CHECK CB?
79M Auto Recl.
No check
Chk each cycle
No check
Check circuit breaker before AR?
7114
T-Start MONITOR
79M Auto Recl.
0.01 .. 320.00 sec;
∞
0.50 sec
AR start-signal monitoring time
7115
CB TIME OUT
79M Auto Recl.
0.10 .. 320.00 sec
3.00 sec
Circuit Breaker (CB) Supervision
Time
7116
Max. DEAD EXT.
79M Auto Recl.
0.50 .. 1800.00 sec;
∞
100.00 sec
Maximum dead time extension
7117
T-ACTION
79M Auto Recl.
0.01 .. 320.00 sec;
∞
∞
sec
Action time
7118
T DEAD DELAY
79M Auto Recl.
0.0 .. 1800.0 sec;
∞
1.0 sec
Maximum Time Delay of Dead-
Time Start
7127
DEADTIME 1: PH
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 1: Phase Fault
7128
DEADTIME 1: G
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 1: Ground Fault
7129
DEADTIME 2: PH
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 2: Phase Fault
7130
DEADTIME 2: G
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 2: Ground Fault
7131
DEADTIME 3: PH
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 3: Phase Fault
7132
DEADTIME 3: G
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 3: Ground Fault
7133
DEADTIME 4: PH
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 4: Phase Fault
7134
DEADTIME 4: G
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 4: Ground Fault
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments