Functions
2.14 Temperature Detection via RTD Boxes
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
204
9034
RTD 3 STAGE 1
-58 .. 482 °F;
∞
212 °F
RTD 3: Temperature Stage 1
Pickup
9035
RTD 3 STAGE 2
-50 .. 250 °C;
∞
120 °C
RTD 3: Temperature Stage 2
Pickup
9036
RTD 3 STAGE 2
-58 .. 482 °F;
∞
248 °F
RTD 3: Temperature Stage 2
Pickup
9041A
RTD 4 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 4: Type
9042A
RTD 4 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 4: Location
9043
RTD 4 STAGE 1
-50 .. 250 °C;
∞
100 °C
RTD 4: Temperature Stage 1
Pickup
9044
RTD 4 STAGE 1
-58 .. 482 °F;
∞
212 °F
RTD 4: Temperature Stage 1
Pickup
9045
RTD 4 STAGE 2
-50 .. 250 °C;
∞
120 °C
RTD 4: Temperature Stage 2
Pickup
9046
RTD 4 STAGE 2
-58 .. 482 °F;
∞
248 °F
RTD 4: Temperature Stage 2
Pickup
9051A
RTD 5 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 5: Type
9052A
RTD 5 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 5: Location
9053
RTD 5 STAGE 1
-50 .. 250 °C;
∞
100 °C
RTD 5: Temperature Stage 1
Pickup
9054
RTD 5 STAGE 1
-58 .. 482 °F;
∞
212 °F
RTD 5: Temperature Stage 1
Pickup
9055
RTD 5 STAGE 2
-50 .. 250 °C;
∞
120 °C
RTD 5: Temperature Stage 2
Pickup
9056
RTD 5 STAGE 2
-58 .. 482 °F;
∞
248 °F
RTD 5: Temperature Stage 2
Pickup
9061A
RTD 6 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 6: Type
9062A
RTD 6 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 6: Location
Addr.
Parameter
Setting Options
Default Setting
Comments