Appendix
A.8 Settings
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
403
235A
ATEX100
P.System Data 1
NO
YES
NO
Storage of th. Replicas w/o
Power Supply
238
Ignd2-CT PRIM
P.System Data 1
1 .. 50000 A
60 A
Ignd2-CT rated primary c. (conn.
to I2)
250A
50/51 2-ph prot
P.System Data 1
ON
OFF
OFF
50, 51 Time Overcurrent with
2ph. prot.
251A
CT Connect.
P.System Data 1
A, B, C, (Gnd)
A,G2,C,G; G->B
A,G2,C,G; G2->B
A, B, C, (Gnd)
CT Connection
260
Ir-52
P.System Data 1
10 .. 50000 A
125 A
Rated Normal Current (52 Break-
er)
261
OP.CYCLES AT Ir
P.System Data 1
100 .. 1000000
10000
Switching Cycles at Rated
Normal Current
262
Isc-52
P.System Data 1
10 .. 100000 A
25000 A
Rated Short-Circuit Breaking
Current
263
OP.CYCLES Isc
P.System Data 1
1 .. 1000
50
Switch. Cycles at Rated Short-
Cir. Curr.
264
Ix EXPONENT
P.System Data 1
1.0 .. 3.0
2.0
Exponent for the Ix-Method
265
Cmd.via control
P.System Data 1
(Setting options depend
on configuration)
None
52 B.Wear: Open Cmd. via
Control Device
266
T 52 BREAKTIME
P.System Data 1
1 .. 600 ms
80 ms
Breaktime (52 Breaker)
267
T 52 OPENING
P.System Data 1
1 .. 500 ms
65 ms
Opening Time (52 Breaker)
276
TEMP. UNIT
P.System Data 1
Celsius
Fahrenheit
Celsius
Unit of temperature measure-
ment
280
Holmgr. for
Σ
i
P.System Data 1
NO
YES
NO
Holmgreen-conn. (for fast sum-i-
monit.)
302
CHANGE
Change Group
Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A
Change to Another Setting
Group
401
WAVEFORMTRIGGER
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup
Waveform Capture
402
WAVEFORM DATA
Osc. Fault Rec.
Fault event
Pow.Sys.Flt.
Fault event
Scope of Waveform Data
403
MAX. LENGTH
Osc. Fault Rec.
0.30 .. 5.00 sec
2.00 sec
Max. length of a Waveform
Capture Record
404
PRE. TRIG. TIME
Osc. Fault Rec.
0.05 .. 0.50 sec
0.25 sec
Captured Waveform Prior to
Trigger
405
POST REC. TIME
Osc. Fault Rec.
0.05 .. 0.50 sec
0.10 sec
Captured Waveform after Event
406
BinIn CAPT.TIME
Osc. Fault Rec.
0.10 .. 5.00 sec;
∞
0.50 sec
Capture Time via Binary Input
610
FltDisp.LED/LCD
Device, General
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
613A
50N/51N/67N w.
P.System Data 1
Ignd (measured)
3I0 (calcul.)
Ignd (measured)
50N/51N/67N Ground Overcur-
rent with
640
Start image DD
Device, General
image 1
image 2
image 3
image 4
image 1
Start image Default Display
1102
FullScaleCurr.
P.System Data 2
10 .. 50000 A
100 A
Measurem:FullScaleCur-
rent(Equipm.rating)
1107
I MOTOR START
P.System Data 2
1A
0.40 .. 10.00 A
2.50 A
Motor Start Current (Block 49,
Start 48)
5A
2.00 .. 50.00 A
12.50 A
1201
FCT 50/51
50/51 Overcur.
ON
OFF
ON
50, 51 Phase Time Overcurrent
1202
50-2 PICKUP
50/51 Overcur.
1A
0.10 .. 35.00 A;
∞
2.00 A
50-2 Pickup
5A
0.50 .. 175.00 A;
∞
10.00 A
1203
50-2 DELAY
50/51 Overcur.
0.00 .. 60.00 sec;
∞
0.00 sec
50-2 Time Delay
1204
50-1 PICKUP
50/51 Overcur.
1A
0.10 .. 35.00 A;
∞
1.00 A
50-1 Pickup
5A
0.50 .. 175.00 A;
∞
5.00 A
1205
50-1 DELAY
50/51 Overcur.
0.00 .. 60.00 sec;
∞
0.50 sec
50-1 Time Delay
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments