Appendix
A.8 Settings
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
406
1907
51Nc T-DIAL
ColdLoadPickup
0.50 .. 15.00 ;
∞
5.00
51Nc Time Dial
1908
50Nc-3 PICKUP
ColdLoadPickup
0.25 .. 35.00 A;
∞
∞
A
50Nc-3 Pickup
1909
50Nc-3 DELAY
ColdLoadPickup
0.00 .. 60.00 sec;
∞
0.00 sec
50Nc-3 Time Delay
2201
INRUSH REST.
50/51 Overcur.
OFF
ON
OFF
Inrush Restraint
2202
2nd HARMONIC
50/51 Overcur.
10 .. 45 %
15 %
2nd. harmonic in % of fundamen-
tal
2203
CROSS BLOCK
50/51 Overcur.
NO
YES
NO
Cross Block
2204
CROSS BLK TIMER
50/51 Overcur.
0.00 .. 180.00 sec
0.00 sec
Cross Block Time
2205
I Max
50/51 Overcur.
1A
0.30 .. 25.00 A
7.50 A
Maximum Current for Inrush Re-
straint
5A
1.50 .. 125.00 A
37.50 A
2701
50 1Ph
50 1Ph
OFF
ON
OFF
50 1Ph
2702
50 1Ph-2 PICKUP
50 1Ph
1A
0.05 .. 35.00 A;
∞
0.50 A
50 1Ph-2 Pickup
5A
0.25 .. 175.00 A;
∞
2.50 A
2703
50 1Ph-2 PICKUP
50 1Ph
0.003 .. 1.500 A;
∞
0.300 A
50 1Ph-2 Pickup
2704
50 1Ph-2 DELAY
50 1Ph
0.00 .. 60.00 sec;
∞
0.10 sec
50 1Ph-2 Time Delay
2705
50 1Ph-1 PICKUP
50 1Ph
1A
0.05 .. 35.00 A;
∞
0.20 A
50 1Ph-1 Pickup
5A
0.25 .. 175.00 A;
∞
1.00 A
2706
50 1Ph-1 PICKUP
50 1Ph
0.003 .. 1.500 A;
∞
0.100 A
50 1Ph-1 Pickup
2707
50 1Ph-1 DELAY
50 1Ph
0.00 .. 60.00 sec;
∞
0.50 sec
50 1Ph-1 Time Delay
3101
Sens. Gnd Fault
Sens. Gnd Fault
OFF
ON
OFF
(Sensitive) Ground Fault
3113
50Ns-2 PICKUP
Sens. Gnd Fault
0.001 .. 1.500 A
0.300 A
50Ns-2 Pickup
3113
50Ns-2 PICKUP
Sens. Gnd Fault
1A
0.05 .. 35.00 A
10.00 A
50Ns-2 Pickup
5A
0.25 .. 175.00 A
50.00 A
3114
50Ns-2 DELAY
Sens. Gnd Fault
0.00 .. 320.00 sec;
∞
1.00 sec
50Ns-2 Time Delay
3117
50Ns-1 PICKUP
Sens. Gnd Fault
0.001 .. 1.500 A
0.100 A
50Ns-1 Pickup
3117
50Ns-1 PICKUP
Sens. Gnd Fault
1A
0.05 .. 35.00 A
2.00 A
50Ns-1 Pickup
5A
0.25 .. 175.00 A
10.00 A
3118
50Ns-1 DELAY
Sens. Gnd Fault
0.00 .. 320.00 sec;
∞
2.00 sec
50Ns-1 Time delay
3119
51Ns PICKUP
Sens. Gnd Fault
0.001 .. 1.400 A
0.100 A
51Ns Pickup
3119
51Ns PICKUP
Sens. Gnd Fault
0.003 .. 0.500 A
0.004 A
51Ns Pickup
3119
51Ns PICKUP
Sens. Gnd Fault
1A
0.05 .. 4.00 A
1.00 A
51Ns Pickup
5A
0.25 .. 20.00 A
5.00 A
3120
51NsTIME DIAL
Sens. Gnd Fault
0.10 .. 4.00 sec;
∞
1.00 sec
51Ns Time Dial
3121A
50Ns T DROP-OUT
Sens. Gnd Fault
0.00 .. 60.00 sec
0.00 sec
50Ns Drop-Out Time Delay
3127
51Ns I T min
Sens. Gnd Fault
0.003 .. 1.400 A
1.333 A
51Ns Current at const. Time
Delay T min
3127
51Ns I T min
Sens. Gnd Fault
1A
0.05 .. 20.00 A
15.00 A
51Ns Current at const. Time
Delay T min
5A
0.25 .. 100.00 A
75.00 A
3128
51Ns I T knee
Sens. Gnd Fault
0.003 .. 0.650 A
0.040 A
51Ns Current at Knee Point
3128
51Ns I T knee
Sens. Gnd Fault
1A
0.05 .. 17.00 A
5.00 A
51Ns Current at Knee Point
5A
0.25 .. 85.00 A
25.00 A
3129
51Ns T knee
Sens. Gnd Fault
0.20 .. 100.00 sec
23.60 sec
51Ns Time Delay at Knee Point
3131
M.of PU TD
Sens. Gnd Fault
1.00 .. 20.00 MofPU;
∞
0.01 .. 999.00 TD
Multiples of PU Time-Dial
3132
51Ns TD
Sens. Gnd Fault
0.05 .. 1.50
0.20
51Ns Time Dial
3140
51Ns Tmin
Sens. Gnd Fault
0.00 .. 30.00 sec
1.20 sec
51Ns Minimum Time Delay
3140
51Ns T min
Sens. Gnd Fault
0.10 .. 30.00 sec
0.80 sec
51Ns Minimum Time Delay
3141
51Ns Tmax
Sens. Gnd Fault
0.00 .. 30.00 sec
5.80 sec
51Ns Maximum Time Delay
3141
51Ns T max
Sens. Gnd Fault
0.50 .. 200.00 sec
93.00 sec
51Ns Maximum Time Delay (at
51Ns PU)
3142
51Ns TIME DIAL
Sens. Gnd Fault
0.05 .. 15.00 sec;
∞
1.35 sec
51Ns Time Dial
3143
51Ns Startpoint
Sens. Gnd Fault
1.0 .. 4.0
1.1
51Ns Start Point of Inverse
Charac.
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments