Functions
2.1 General
SIPROTEC, 7SJ61, Manual
C53000-G1140-C210-1, Release date 02.2008
33
2.1.2.3
Settings
2.1.2.4
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
610
FltDisp.LED/LCD
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
640
Start image DD
image 1
image 2
image 3
image 4
image 1
Start image Default Display
No.
Information
Type of In-
formation
Comments
-
>Light on
SP
>Back Light on
-
Reset LED
IntSP
Reset LED
-
DataStop
IntSP
Stop data transmission
-
Test mode
IntSP
Test mode
-
Feeder gnd
IntSP
Feeder GROUNDED
-
Brk OPENED
IntSP
Breaker OPENED
-
HWTestMod
IntSP
Hardware Test Mode
-
SynchClock
IntSP_Ev
Clock Synchronization
-
Error FMS1
OUT
Error FMS FO 1
-
Error FMS2
OUT
Error FMS FO 2
-
Distur.CFC
OUT
Disturbance CFC
1
Not configured
SP
No Function configured
2
Non Existent
SP
Function Not Available
3
>Time Synch
SP_Ev
>Synchronize Internal Real Time Clock
5
>Reset LED
SP
>Reset LED
15
>Test mode
SP
>Test mode
16
>DataStop
SP
>Stop data transmission
51
Device OK
OUT
Device is Operational and Protecting
52
ProtActive
IntSP
At Least 1 Protection Funct. is Active
55
Reset Device
OUT
Reset Device
56
Initial Start
OUT
Initial Start of Device
67
Resume
OUT
Resume
68
Clock SyncError
OUT
Clock Synchronization Error
69
DayLightSavTime
OUT
Daylight Saving Time
70
Settings Calc.
OUT
Setting calculation is running
71
Settings Check
OUT
Settings Check
72
Level-2 change
OUT
Level-2 change
73
Local change
OUT
Local setting change
110
Event Lost
OUT_Ev
Event lost
113
Flag Lost
OUT
Flag Lost
125
Chatter ON
OUT
Chatter ON
140
Error Sum Alarm
OUT
Error with a summary alarm
144
Error 5V
OUT
Error 5V