Differential Protection Pickup Logic and Tripping Logic
Functional Description
Pickup Logic
Once the differential protection function has reliably registered a fault within its tripping zone, the signal
87(N)L Gen.Flt.
(general pickup of the differential protection) is generated. For the differential protection
function itself, this pickup signal is of no concern since the tripping conditions are available at the same time.
This signal, however, is required to initiate the internal or external supplementary functions, e.g. fault
recording, automatic reclosing.
[lo-diff-g-anr-20110304, 1, en_US]
Figure 2-15
General pickup
Tripping Logic
The following figure shows the tripping logic of the differential protection.
[lo-esd-erd-aus-20101117, 2, en_US]
Figure 2-16
Differential protection trip
If the pickup signals apply for longer than the configurable trip time delay, the differential protection trips.
2.2.5
2.2.5.1
Functions
2.2 Phase Comparison Protection and Ground Differential Protection
62
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...