Frequency Protection (Optional)
Frequency Elements
Quantity
4, depending on setting effective on f< or f>
Pickup Values
f> or f< adjustable for each element
at f
Nom
= 50 Hz
45.50 Hz to 54.50 Hz
Increments 0.01 Hz
at f
Nom
= 60 Hz
55.50 Hz to 64.50 Hz
Increments 0.01 Hz
Times
Pickup times f>, f<
approx. 85 ms
Dropout times f>, f<
approx. 30 ms
Time delays T
0,00 s to 600,00 s
Increments 0,01 s
The set times are pure time delays.
Note on drop-off times:
Drop-off was enforced by current = 0 A and voltage = 0 V.
Enforcing the drop-off by means of a frequency change below the drop-off threshold extends the drop-off times.
Dropout Difference
Δf =
Ι
pickup value - dropout value
Ι
0.02 Hz to 1 Hz
Operating Ranges
In voltage range
approx. 0.65 · V
N
to 230 V (phase-to-phase)
In frequency range
25 Hz to 70 Hz
Tolerances
Frequencies f>, f< in specific range (f
Nom
± 10 %)
15 mHz in range V
PhPh
: 50 V to 230 V
Time delays T(f<, f>)
1 % of setting value or 10 ms
4.12
Technical Data
4.12 Frequency Protection (Optional)
SIPROTEC 4, 7SD80, Manual
281
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...