Monitoring Functions
Measured Values
Current sum
Ι
F
= |
Ι
A
+
Ι
B
+
Ι
C
+ k
Ι
·
Ι
E
| >
SUM.I TRESHOLD ·
Ι
N
+ SUM.FACTOR
Ι
·Σ |
Ι
|
- SUM.
Ι
TRESHOLD
for
Ι
Nom
= 1 A 0.10 A to 2.00 A
Increments 0.01 A
for
Ι
Nom
= 5 A 0.50 A to 10.00 A
Increments 0.01 A
- SUM.FACTOR
Ι
0.00 to 0.95
Increments 0.01
Current symmetry
|
Ι
min
|/|
Ι
max
| < BAL.FACTOR
Ι
as long as
Ι
max
/
Ι
N
> BAL.
Ι
LIMIT/
Ι
N
- BAL.FACTOR
Ι
0.10 to 0.95
Increments 0.01
- BAL.
Ι
LIMIT
for
Ι
Nom
= 1 A 0.10 A to 1.00 A
Increments 0.01 A
for
Ι
Nom
= 5 A 0.50 A to 5.00 A
Increments 0.01 A
- T BAL.
Ι
LIMIT
5 s to 100 s
Increments 1 s
Broken conductor
one conductor without current, the others with current
(monitoring of current transformer circuits on current step
change in one phase without residual current)
Voltage Balance
| V
min
|/| V
max
| < SYM.FAK.V
as long as | V
max
| > SYM.VGRENZ
- BAL.FACTORV
0.58 to 0.95
Increments 0.01
- BAL.VLIMIT
10 V to 100 V
Increments 1 V
- T BAL.VLIMIT
5 s to 100 s
Increments 1 s
Voltage phase sequence
V
A
leads V
B
leads V
C
as long as | V
A
|, | V
B
| , | V
C
| > 40 V/√3
non-symmetrical voltages
(Fuse-Failure-Monitor)
3 · V
0
> FFM V> ODER 3 · V
2
> FFM V>
AND at the same time
3 ·
Ι
0
< FFM
Ι
< AND 3 ·
Ι
2
< FFM
Ι
<
- FFM V>
10 V to 100 V
Increments 1 V
- FFM
Ι
<
for
Ι
Nom
= 1 A 0.10 A to 1.00 A
Increments 0.01 A
for
Ι
Nom
= 5 A 0.50 A to 5.00 A
Increments 0.01 A
three-phase measuring voltage failure
(Fuse-Failure-Monitor)
all V
Ph-E
< FFM VMESS <
AND at the same time
all Δ
Ι
Ph
< FFM
Ι
delta
AND
all
Ι
Ph
> (
Ι
Ph
> (Dist.))
OR
all V
Ph-E
< FFM VMESS <
AND at the same time
alle
Ι
Ph
< (
Ι
Ph
> (Dist.))
AND
alle
Ι
Ph
> 40 mA
- FFM VMEAS <
2 V to 100 V
Increments 1 V
4.15
Technical Data
4.15 Monitoring Functions
284
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...