Breaker Intertrip and Remote Tripping- Direct Local Trip
Breaker Intertrip and Remote Tripping
Transfer trip of the opposite end for single-end tripping
can be switched on/off
External Direct Trip
Operating time, total
approx. 6 ms
Trip time delay
Trip Time DELAY
minimum
14 ms
typical
17 ms
maximum
20 ms
Dropout times
minimum
25 ms
typical
27 ms
maximum
29 ms
Expiry tolerances
1 % of setting value or 10 ms
The set times are pure time delays
Remote Trip
Tripping of the remote ends by a command injected via binary inputs
The command times depend on the communication speed.
The following data require a transmission rate of 512 kbit/s for the optical fiber protection interface.
Operating times, total approx.
minimum
10 ms
typical
13 ms
maximum
15 ms
Dropout times
minimum
26 ms
typical
27 ms
maximum
29 ms
Tripping delay
85 DT: TD-BI
0.00 s to 30.00 s
Increments 0.01 s
Trip time prolongation
85 DT:T-PROL
BI
0.00 s to 30.00 s
Increments 0.01 s
Expiry tolerances
1 % of setting value or 10 ms
The set times are pure time delays
4.6
Technical Data
4.6 Breaker Intertrip and Remote Tripping- Direct Local Trip
266
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...