● The computer to be monitored must be configured in the config.ini configuration file of the
TCU according to the general configuration for a TCU in a separate host section as a
switchover target for this TCU.
Where necessary, a password has to be specified in the configuration, if the VNC server
requires one on the target system (see below).
● To ensure that the TCU recognizes the new switchover target, the TCU requires a restart
and reboot.
● The screen resolution of the computer to be monitored must be adjusted to the conditions
of the TCU, since otherwise the TCU scales the image received to its possible range of
representation, which would adversely affect the representation on the TCU.
Configuration
1&8
7&8
6\VWHPQHWZRUN
1HWZRUN
3*3&
;
;
Figure 1-25
Configuration example
Configuration
The config.ini file is located in the following directory:
NCU:
/user/common/tcu/<TCU name>/common/tcu
PCU (Windows XP):
F:\user_base\common\tcu\<TCU name>\common\tcu
PCU (Windows 7):
C:\ProgramData\Siemens\MotionControl\user\common
\tcu\<TCU name>\common\tcu
The config.ini file must be stored on the boot server (active DHCP).
Example:
[Station]
General information and networking
1.4 Networking
Operator panel front: OP 010
Manual, 07/2018, A5E36371538B
83