Installing and putting a SINAUT modem into operation
5.8 ISDN dial-up modem MD4
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
265
Table 5- 45 Overview of the configurable standard profiles for dialing mode
Profile no. Description of the profile
Profile setting on DIL switch
SW1 (SW1.3 = ON)
0
AT command set
Data format:
•
In the command phase: Self-adapting
•
In the data phase: 10 bits (8N1)
(factory default)
2))
21
1
V.25bis,
1200 bps V.23 hx
Data format:
•
In the command phase: 10 bits (7E1)
•
In the data phase: 11 bits (8E1)
2))
21
2
V.25bis,
2400 bps V.22bis
Data format:
•
In the command phase: 10 bits (7E1)
•
In the data phase: 11 bits (8E1)
2))
21
3
V.25bis,
9600 bps V.32
Data format:
•
In the command phase: 10 bits (7E1)
•
In the data phase: 11 bits (8E1)
2))
21
Resetting the modem
If the configuration of the modem is unclear, you can reset to the factory default settings.
When you reset the modem, all four standard profiles for dialing mode are reset to the
factory defaults.
Procedure:
1.
Power supply OFF
2.
Set switch 3 to ON and switch 1, 2 and 4 to OFF
3.
Power supply ON and then wait until the lower four LEDs have stopped flashing in
sequence.