Installation guide
3.5 Installing the TIM 4R-IE in an S7-300
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
111
Compact CPU modules
CPU 312C
as of 6ES7 312-5BD00-0AB0
CPU 313C
as of 6ES7 313-5BE00-0AB0
CPU 313C-2PtP
as of 6ES7 313-6BE00-0AB0
CPU 313C-2DP
as of 6ES7 313-6CE00-0AB0
CPU 314C-2PtP
as of 6ES7 314-6BF00-0AB0
CPU 314C-2DP
as of 6ES7 314-6CF00-0AB0
Instead of an S7-300 standard or compact CPU, one of the following C7 control systems
may also be used.
C7 control systems
C7-613
as of 6ES7 613-1CA00-0AE3
(C7-623/P)
as of 6ES7 623-1DE01-0AE3
(C7-626/P)
as of 6ES7 626-1DG02-0AB3
(C7-626/P DP)
as of 6ES7 626-2DG02-0AB3
(C7-633/P)
as of 6ES7 633-1DF00-0AB3
(C7-633/DP)
as of 6ES7 633-2BF00-0AB3
(C7-634/P)
as of 6ES7 634-1DF00-0AB3
(C7-634/DP)
as of 6ES7 634-2BF00-0AB3
C7-635 Key
as of 6ES7 635-2EC00-0AB3
C7-635 Touch
as of 6ES7 635-2EB00-0AB3
C7-636 Key
as of 6ES7 636-2EC00-0AB3
C7-636 Touch
as of 6ES7 636-2EB00-0AB3
Installation in a rack
With standard and compact CPU modules, the TIM can be inserted into any of the racks 0 to
3 but only in expansion racks 1 to 3 if these racks are connected to the CPU over the IM
360/IM 361 interface modules.
With the C7 control systems, the TIM can be inserted in any of the expansion racks 1 to 3.
These are connected to the C7 device over IM 360/IM 361 interface modules (the IM 360 is
already integrated in the C7 device). With the C7-635 and C7-636 devices, this is also
possible without the IM 361 if no more than four modules including the TIM are connected
externally.
For all S7-300 racks the following applies: All slots designed for SM, FM or CP can also be
used for the TIM.
A bus module connector ships with every TIM. The TIM is connected to the module to its left
by the bus module connector.
If a SINAUT modem of the type MD2, MD3 or MD4 is used, this can be installed on a
separate S7-300 rail or on a 35 mm DIN rail (an adapter is available). To save space, it can
also be installed in a free slot of racks 0 to 3. This modem is connected over the RS-232 port
of the TIM using a standard connecting cable, type 6NH7701-xxx.