Connection
4.8 Cables and connections
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
49
Cable, connectors and tools specifications
The detailed specifications for the cables, connectors and tools required to manufacture the
necessary cables for the SINAMICS G110D are listed in the following tables.
Note
NFPA compatibility
These devices are intended only for installation on industrial machines in accordance with
the "Electrical Standard for Industrial Machinery" (NFPA79). Due to the nature of these
devices they may not be suitable for installation in accordance with the "National Electrical
Code" (NFPA70).
Table 4- 11 Tools
Harting part number
Crimp tool (Q8/0 and Q4/2)
0999-000-0110
Removal tool (Q8/0)
0999-000-0319
Removal tool (Q4/2)
0999-000-0305
No special tools are required for the Control Unit connectors
Table 4- 12 Control Unit connectors
Connector
Binder part numbers
Straight connector
Right-angle connector
ASI (M12 )
99-0436-14-05
99-0436-24-05
Digital input and Analog output (M12 )
99-0437-14-05
99-0437-24-05
Table 4- 13 Mains supply connector
Power
rating
cable size cable type
All connector parts are Harting Q4/2
Shell
Crimp
size
Crimp number
Hood
Gland/Seal
0.75 kW 1.5 mm
2
16 AWG
(3+E) YY
Unscreened
Harting Q4/2
0912 006 3141
1.5 mm
2
16 AWG
0932 000 6204 0912 008 0527 0900 000 5059
1.50 kW
3.00 kW 2.5 mm
2
14 AWG
(3+E) YY
Unscreened
2.5 mm
2
14 AWG
0932 000 6205 1912 008 0526 1900 000 5190
4.00 kW
5.50 kW 4 mm
2
12 or 10
AWG
(3+E) YY
Unscreened
4 mm
2
12 or 10
AWG
0932 000 6207
7.50 kW
4 x crimps are required for each inverter; use 75°C copper wire only
Summary of Contents for SINAMICS G110D
Page 1: ......
Page 2: ......
Page 8: ...Table of contents SINAMICS G110D 8 Operating Instructions 07 2016 FW V3 63 A5E36768472B AB ...
Page 223: ......
Page 224: ......