Functions
6.4 Setpoint sources
SINAMICS G110D
106
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
6.4.2
Frequency setpoint using analog input [P1000=2]
Frequency setpoint using analog input [for P1000 = 2]
Analog setpoints are read-in using the analog input. The setting specifying whether the
analog input is a voltage input (10 V) or voltage input (10 V) with monitoring must be made
using P0756.
Depending on the AI type of the source, a suitable connection must be established.
Table 6- 17 Set and parameterize the analog input for use as setpoint source
Analog input
Parameters
Description
Setting the DIP
switch
AI0+
P0756 [0]
Analog input 0
AI0-
P0756 = 0
Analog input type (AI)
Defines the analog input type and enables analog input monitor-
ing.
0: Unipolar voltage input (0 … +10 V) (factory setting)
1: Unipolar voltage input with monitoring (0 … +10 V)
P0757 = 0
Value x1 for AI scaling [V or mA]
P0758 = 0.0
Value y1 of AI-scaling
This parameter shows the amount of x1 as a % of P2000 (refer-
ence frequency)
P0761 = 0
Width of the AI dead zone