Functions
6.4 Setpoint sources
SINAMICS G110D
108
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
6.4.4
Using fixed frequencies as a setpoint source
Frequency setpoint via fixed frequency (P1000 = 3)
The fixed frequencies are defined using parameters P1001 to P1004 and can be assigned to
the corresponding digital inputs using P1020 to P1023.
The fixed frequency can be selected using digital input 3 by default. However, the
assignment of fixed frequencies can be configured to use any of the other digital inputs on
the Inverter. An example is given below of selecting two fixed frequencies using digital input
2 and 3.
Table 6- 20 Parameters to directly select frequencies
Parameters
Description
P1016 = 1
Fixed frequency mode, defines the procedure for selecting fixed frequencies.
1: Direct selection (factory setting)
2: Binary-coded selection
P1001 = 50
Fixed frequency 1 (FF1) (FF values in Hz)
P1002 = -50
Fixed frequency 2 (FF2)
P1003 = 10
Fixed frequency 3 (FF3)
P1004 = 15
Fixed frequency 4 (FF4)
P1020 = 2091.0 FF1 selection using fieldbus
Additional information about binary coded selection of the fixed frequencies (P1016 = 2) is
provided in function chart 3210 of the List Manual.
Table 6- 21 Example: Selecting 2 fixed frequencies using digital input 2 and digital input 3
Parameter
Description
P0003 = 3
Enable expert access to parameters
P0700 = 2
Selecting the command source: Digital inputs
P0701 = 1
ON/OFF1 (DI0) - factory setting
P0702 = 12
Direction reversal (DI1) - factory setting
P0703 = 99
Enable / 'open' digital input 2 (DI2)
P0704 = 99
Enable / 'open' digital input 3 (DI3)
P1001 = 4.00
Defines fixed frequency 1 (FF1) in [Hz]
P1002 = 8.00
Defines fixed frequency 2 (FF2) in [Hz]
P1020 = 2091.0
Connect fixed frequency 1(FF1) with the status of DI2.
2091.0 = Parameter, which displays the status of digital input 2.
P1021 = 2091.1
Connect fixed frequency 2(FF2) with the status of DI3.
2091.1 = Parameter, which displays the status of digital input 3.