Functions
6.11 Operation in fieldbus systems
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
195
Application parameters
Using the "Expert List" mode in STARTER (as previously described) the following
parameters should be modified as shown in the table below. Before setting the parameters
listed below, you must wait until P3900 = 0.
In addition to the AS-i specific parameters discussed in the previous section the following
parameters should be modified to allow the digital inputs to be read by the controlling PLC.
Table 6- 68 Conveyor application parameters
Parameter Setting Description
P0701 [0] 22
Digital input DI0 set to Quick Stop source 1 allowing DI0 to be used as Quick
Stop input
P0971
1
Transfers parameter values from RAM to EEPROM
Example S7 script and ladder logic
The following is an example S7 script which the PLC will use to communicate with the
Inverter.
Image 6-54 Example S7 script