Functions
6.11 Operation in fieldbus systems
SINAMICS G110D
160
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
connected to the part of the AS-i network furthest from the power unit. Only one power unit is
required to power the slaves on the segement up to 200 m (656 ft).
6.11.1.3
Example: configuring the Inverter on the AS-i network
Example: configuring the Inverter on an AS-i network
Task
To integrate the Inverter on an existing AS-i network under the control of an AS-i master.
The control signals and speed setpoints will be transferred thourgh the AS-i master to the
Inverter. In the other direction, the Inverter is to transfer its status messages and actual
speed value to the higher-level controller through the AS-i master.
What prior knowledge is required?
This section does not explain how to use the higher-level controller or the varius software
engineering tools.
Hardware components (example)
Component
Type
Order no.
Qty
AS-i devices and cables
AS-i Master
CP343-2
6GK7343-2AH01-0XA0
1
AS-i Power supply unit
-
3RX9-501-0BA00
1
AS-i Cable Trapezoidal
Yellow
3RX9013-0AA00
See note 1
AS-i Cable Trapezoidal
Black
3RX9023-0AA00
See note 1
AS-i M12 connection kit
-
3RK1901-1NR21
1
Inverter
SINAMICS G110D
Frame size A - 0.75 kW
6SL3511-0PE17-5AM0
See note 2
IOP
Intelligent Operator Panel
6SL3255-0AA00-4AA0
1
Motor
Standard motor
Three-phase induction motor
1LA7060-4AB10
1
Notes:
1. Cable length depends on the user requirements and cannot be specified.
2. Although the SINAMICS G110D FSA Inverter is specified, all the SINAMICS G110D Inverters are configured in the
same manner