12.2010
Commissioning
Siemens AG 6RX1700-0DD74
ENGLISH
65
SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
5.
Determining the maximum energy in the armature circuit for the turn-off operation
Parameter value required:
p51570
MLFB (Order No.) of the SIMOREG CCP
r50072[1]
actual rated unit DC current, armature [A]
r50101
rated motor armature voltage [V]
1.)
p50111
Armature circuit inductance [mH]
as well as a characteristic diagram according to the following table:
MLFB
SIMOREG CCP
MLFB
characteristi
c number
p50101 [V]
1.)
No. of the associated
characteristic diagram
2.)
420 11
6RA7085-6FC00-0
250
470 12
420 11
6RA7091-6FC00-0
251
470 12
420 13
6RA7095-6FC00-0
252
520 14.0
600 14
6RA7090-6KC00-0
253
720 15
520 16.0
600 16
6RA7095-6KC00-0
254
720 17
1.) Rated DC voltage according to the motor rating plate (the values are typical rated data
for Siemens DC motors from the product catalog DA12
2.) The characteristic diagrams are provided in the appendix to these operating instructions
If the graphically determined value lies below the limit line W_max, then the energy reduction
in the armature circuit is assured using the SIMOREG CCP.
6.
Determining the setting value for parameter p51578 (factory setting = 145)
Required parameter values:
p51570
MLFB (Order No.) of the SIMOREG CCP
r50071
Rated unit supply voltage (armature) [V]
r50072[1]
actual rated unit DC current, armature [A]
r50078[0]
actual rated converter input voltage, armature [V]
r50101
rated motor armature voltage [V]
p50111
armature circuit inductance [mH]
p50351
Threshold for the undervoltage shutdown [%].
⇒
Determining the setting value according to the parameter description for p51578
The SIMOREG CCP is now ready to run.