Commissioning
Siemens AG 6RX1700-0DD74
ENGLISH
43
SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
PNU
Description
Value range
[dimension]
Graduation
No. of
indices
Factory
setting (FS)
Type
See/
change
(Access /
state)
n572
(2572)
Rated current of the SIMOREG CCP
[from SW 2.1 and higher]
Rated current of the SIMOREG CCP stamped on the rating plate
0.0 to 6553.5
[A]
0.1A
Ind: None
Type: O2
P052 = 3
State of the SIMOREG CCP
[from SW 2.2 and higher]
Display at the operator panel (PMU):
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segment lit or bit = 1: significance specified below applies
Segment dark or bit = 0:
significance specified below does not apply
Segment or bit
0 Voltage at U, V, W is OK
1 Voltage at C – D greater than +100 V
2 Voltage at C – D less than -100 V
3 The quenching capacitors have reached the setpoint
voltage
4 Turn-off operation running
5 Connection between parallel SIMOREG CCP OK
6
-
7
-
8 Parallel interface connected at CCP
9 I2t value of voltage limiting chopper 1 is too high
10 I2t value of voltage limiting chopper 2 is too high
11 Contents of the memory of the technical data of the
SIMOREG CCP (MLFB, rated values, serial number)
valid
12 Pre-charging of the chopper capacitors completed
13
14
15
-
-
-
n574
(2574)
Note:
This parameter has the same bit assignment as connector K0574.
Ind: None
Type: V2
P052 = 3
n575
(2575)
Display of the I2t value
[from SW 2.1]
of the voltage limitingchoppers 1 of the SIMOREG CCP
0 to 100
[%]
1 %
Ind: None
Type: O2
P052 = 3
n576
(2576)
Display of the I2t value
[from SW 2.1]
of the voltage limitingchoppers 2 of the SIMOREG CCP
0 to 100
[%]
1 %
Ind: None
Type: O2
P052 = 3