Connecting
12.2010
30
ENGLISH
Siemens AG 6RX1700-0DD74
SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
6.2.2 Connecting a SINAMICS DCM
5U
1
5W
1
K1
5N
1
NC
C98043-A7100
C98043-A7125
Power Interface
C98043-A7046
X1
77
X1
65
X1
66
X1
65
X1
72
X2
9_
P
A
R
X3
0_
PA
R
1U
1
1V
1
1W
1
1U
1
1V
1
1W
1
M
1C
1(
1D
1)
1D
1(
1C
1)
L1
L2
L3
3U
1
3W
1
5W
1
5U
1
5N
1
5U
1
5W
1
5N
1
SINAMICS DCM
SIMOREG CCP
2U
1
2V
1
2W
1
X3
00
3C
3D
1C
1(
1D
1)
1D
1(
1C
1)
109 110
XR
1 2 3 4 5
X_SCHÜTZ
1 2 3
XP
1 2 3
XP
<1>
3 AC 380-460 V, 50-60 Hz
3 AC 400-690 V, 50-60 Hz
1 AC 230 V, 50-60 Hz
Fan
Field
Power
supply
Armature
see operating instructions
SINAMICS DCM
or
Power supply
CAUTION
<1>
Operation without a main contactor/circuit breaker is not permissible.
The control voltage for the main contactor (or the circuit breaker) must always be routed via
terminal XR1 (connections 109 and 110) of the SINAMICS DCM and via terminal X_SCHÜTZ
(connections 4 and 5) of the SIMOREG CCP.
For a parallel connection (see Chapter 6.3.2) all SINAMICS DCM units must be incorporated in this
interlock circuit.
In applications with SIMOREG CCP, in the case of a fault, the basic converter unit or the
SIMOREG CCP must be able to safely and reliably disconnect the arrangement from the line
supply.
In addition, it must be carefully observed that the total of the delay times of all of the switching
elements in the control circuit must not exceed the time set at parameter P50089.