SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
F60050 Optimization run interrupted by an internal cause.
Possible error causes
•
Missing connection or interrupted cable at X177
•
For a parallel connection, missing connection or interrupted cable at X165/X166 (parallel interface, master)
•
For a parallel connection, missing connection or interrupted cable at X29_PAR or X30_PAR (turn-off pulse interface)
•
Hardware defect in the charge circuit of the quenching capacitors
•
Ruptured fuse in the armature circuit, either line side or motor side
•
Ruptured fuse in the pre-charging circuit for the chopper capacitors
•
presently in the cooling-down phase necessary for the chopper resistors
•
MLFB data of the SIMOREG CCP (r51570, r51571, r51572) invalid or not available
Fault value:
r50047[0..4]
701 Parameter p50790 P2P-interface, operating mode not
set to communicate with SIMOREG CCP
702 No communication to the CCP
703 p51570 incorrect order number (MLFB) of the CCP
704 Incorrect supply voltage
705 SINAMICS DCM chopper threshold = 0
706 Armature circuit inductance = 0
707 Vmax > as maximum value that can be set for p51578
708 Calculated chopper energy too high
Note regarding fault value = 701:
r50047[1]: Parameter value p50790
Note regarding fault value = 704:
r50047[1]: Parameter value p50078[0]
r50047[2]: Parameter value p51571
r50047[3]: Line supply voltage tolerance SINAMICS DCM
r50047[4]: Line supply voltage tolerance SIMOREG CCP
Note regarding fault value = 707:
r50047[1]: Calculated Vmax
r50047[2]: Parameter p51578 maximum possible value
Note regarding fault value = 708:
r50047[1]: Calculated chopper energy
r50047[2]: maximum possible chopper energy for SIMOREG
CCP