SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions
Detailed description of parameters
PNU
Description
Value range
[dimension]
Graduation
No. of
indices
Factory
setting (FS)
Access
level
r50047
[0...31]
Faults, additional information/fault addit. info
Description:
Display of additional information on faults that have occurred with numbers from
60000 and higher.
[0] =
fault value
[1] =
additional information on the last fault that occurred
(refer to the corresponding fault)
...
[30] = additional information on the last fault that occurred
(refer to the corresponding fault)
[31] = fault number
-
1
1
Ind: 32
-
1
r50071
Rated unit supply voltage armature /
Unit Va_rated
Description:
Displays the unit rated supply voltage for the armature according to the rating
plate of the unit.
-
[Vrms]
-
Ind: None
-
1
p50790
P2P interface operating mode / P2P operating mode
Description:
Sets the operating mode for the peer-to-peer interface (P2P interface).
Value:
0: No function
5: Peer-to-peer communication
6: Communication with SIMOREG CCP
Note:
Correct communication is optically displayed using an LED on the Power
Interface module C98043-A7046:
LED flashes slowly (<1
Hz): Communication with SINAMICS DCM OK
LED flashes quickly (~3
Hz): Communication error with SIMOREG CCP
0 to 6
1
1
Ind: None
FS = 0
2
p50795
P2P/CCP bus termination / P2P/CCP bus term.
Description:
Sets the bus termination for the peer-to-peer interface and the interface to the
SIMOREG CCP.
Value:
0: off
1: on
Note:
CCP: Converter Commutation Protector
P2P: Peer-to-peer interface
0 to 1
1
1
Ind: None
FS = 0
2