Commissioning the device
4.4 Configuring the device
Comfort Panels
Operating Instructions, 03/2012, A5E03404994-02
85
5.
Proceed as in step 4 for all four following positions.
Once you have touched all the positions of the calibration crosshairs, the following dialog
appears:
New calibration settings have been measured.
Tape the screen to register saved data.
Wait for 30 seconds to cancel saved data and
keep the current setting.
Time limit: 30 sec
6.
To apply the calibration, touch the screen within 30 seconds.
Otherwise, the calibration is discarded and the original calibration continues to be used.
When calibration is completed, the "OP Properties" dialog is displayed again.
7.
Close the dialog with "OK".
Result
The touch screen of the HMI device is calibrated.