Monitoring and Response Times of F-Systems
A.4 F-Related Monitoring Times for S7 F/FH Systems
Safety Engineering in SIMATIC S7
A-8
System Manual, 04/2006, A5E00109529-05
A.3.7
Monitoring Time for Safety-Related Communication between F-Runtime Groups
The monitoring time for safety-related communication between F-runtime groups is
determined automatically from the values for the "maximum cycle time" ("Edit F-Runtime
Groups" dialog).
Monitoring time = Maximum cycle time of the 1st F-runtime group + maximum cycle time of
the 2nd F-runtime group
A.4
A.4
F-Related Monitoring Times for S7 F/FH Systems
Monitoring Times to be Configured
The following monitoring times must be configured for S7 F/FH Systems:
Monitored Element ...
F-Block/
in
HW Config
Parameter
Reference ...
F-cycle time of the time
interrupt OB that contains
the safety program
F_CYC_CO
MAX_CYC
"Minimum Monitoring Time
for F-Cycle Time"
Safety-related
communication between
F-CPU and F-I/O via
PROFIsafe (PROFIsafe
monitoring time)
Object properties
dialog in
HW Config
"Monitoring time"
"Minimum Monitoring Time
for Safety-Related
Communication between
F-CPU and F-I/O"
Safety-related
communication between
F-CPUs
F_RCVR, F_RCVBO
F_SENDR,
F_SENDBO
TIMEOUT
"Minimum Monitoring Time
for Safety-Related
Communication between
F-CPUs"
Safety-related
communication between
F-runtime groups
F_R_R
F_R_BO
TIMEOUT
"Minimum Monitoring Time
for Safety-Related
Communication between
F-Runtime Groups"
See also
Minimum Monitoring Time for F-Cycle Time (Page A-9)
Minimum Monitoring Time for Safety-Related Communication between F-CPU and F-I/O
(Page A-11)
Minimum Monitoring Time for Safety-Related Communication between F-CPUs (Page A-13)
Minimum Monitoring Time for Safety-Related Communication between F-Runtime Groups
(Page A-14)