Configuring
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
4-45
Example: Terminating resistor in the MPI subnet
The figure below shows you an example of an MPI subnet and where to install the
terminating resistance.
Terminating resistor on
S7-300
Spur line
OP 27
OP 27
PG
PG*
* connect via spur line only during commisioning / maintenance
RS 485-
Repeater
S7-300
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
S7-300
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
S7-300
SF
BUSF
DC5V
FRCE
FRCE
RUN
STOP
SIEMENS
Figure 4-19 Activation of the terminating resistors in an MPI subnet
Warning
Disturbance of data traffic might occur on the bus.
A bus segment must always be terminated at both ends with the terminating
resistor. This, for example, is not the case if the last slave with bus connector is off
power.
Since the bus connector draws its power from the station, the terminating resistor
has no effect.
Please make sure that power is always supplied to stations on which the
terminating resistor is active.
As an alternative, you can also use the PROFIBUS Terminator as active bus
termination.
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...