Testing functions, Diagnostics and Fault Elimination
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
10-13
Diagnostic Addresses
With CPU 31x-2 you assign diagnostic addresses for the PROFIBUS-DP. Make
sure during configuration that DP diagnostic addresses are assigned to the DP
master and to the DP slave.
When you configure ithe DP
masters, you have to specify (in
the associated project of the
DP masters) a diagnostic
address for the DP slave. In the
following, this diagnostic address
is refered to as
.
The DP master recieves
information on the status of the
DP slaves or on a bus
interruption via this diagnostic
address.
allocated to the
DP master
When you configure the DP slaves
you must also specify (in the
associated projects of the DP
slaves) a diagnostic address that is
allocated to the DP slave. In the
following, the diagnostic address is
refered to
as allocated to the DP
slave.
The DP slave receives information
on the status of the DP masters or
on a bus interruption via this
diagnostic address.
CPU as DP master
CPU as DP slave
During configuration you must specify two diagnostic addresses:
PROFIBUS DP
Diagnostic address
Diagnostic address
Figure 10-4 Diagnostic addresses for DP masters and DP slaves
Special features of CPUs 31xC-2DP
With CPUs 31xC-2DP operating as master, assign two different diagnostic
addresses to one I-Slave, one diagnostic address to slot 0 and one diagnostic
address to slot 2. These two addresses have the following functions:
•
The diagnostic address for slot 0 reports in the master all events relating to the
complete slave (station representative), e.g. station failure.
•
The diagnostic address for slot 2 is used to report events at this slot, that is,
with the CPU operating as I-Slave it reports the diagnostic interrupts for
operating state transitions.
Event Recognition
The table below shows how CPU 31x-2 operating as DP master recognizes
operating mode transitions of a CPU operating as DP slave or data exchange
interruptions.
Table 10-8
Event recognition of CPU 31x-2 operating as DP master
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...