Commissioning
S7-300 Programmable Controller Hardware and Installation
8-26
A5E00105492-01
8.7.2
Commissioning the CPU as DP Master
Prerequisites for commissioning
•
The PROFIBUS subnet has been configured.
•
The DP slaves are ready for operation (see relevant DP slave manual).
•
An MPI/DP interface as DP interface must be configured accordingly (only CPU
318-2).
•
You must configure the CPU as DP master prior to commissioning. That is, in
STEP 7 you must:
–
configure the CPU as a DP master,
–
assign a PROFIBUS address to the CPU,
–
assign a master diagnostic address to the CPU,
–
integrate the DP slaves into the DP master system.
Is a CPU 31x-2 DP/31xC-2 DP a DP Slave?
If so, you will find that DP slave in the PROFIBUS-DP catalog as already
configured station. In the DP master, assign a slave diagnostic address to
this DP Slave CPU. You must interconnect the DP master with the DP slave
CPU and specify the address areas for data exchange with the DP slave
CPU.
Commissioning
Commission CPU 31x-2 DP/31xC-2 DP as DP master in the PROFIBUS subnet as
follows:
1. Download the PROFIBUS subnet configuration (preset configuration) you have
created in STEP 7 from the PG to CPU 31x-2 DP/31xC-2 DP.
2. Switch on all of the DP slaves.
3. Switch CPU 31x-2 DP/31xC-2 DP from STOP to RUN mode.
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...