Appendix
S7-300 Programmable Controller Hardware and Installation
11-16
A5E00105492-01
Cables for ...
and cables for ...
Run ...
•
Bus signals, shielded
(PROFIBUS)
•
Data signals, shielded
(programming devices,
operator panels, printers,
counter inputs, etc.)
•
Analog
signals,
shielded
•
DC voltage (
≤
60 V),
unshielded
•
Process
signals
(
≤
25 V),
shielded
•
AC voltage (
≤
25 V),
unshielded
•
Monitors (coaxial cable)
In separate bundles or cable
ducts (no minimum clearance
necessary)
•
DC voltage (> 60 V and
≤
400 V), unshielded
•
AC voltage (> 25 V and
≤
400 V), unshielded
In common bundles or cable
ducts
•
DC voltage (> 60 V and
≤
400 V), unshielded
•
AC voltage (> 25 V and
≤
400 V), unshielded
•
DC and AC voltage (> 400 V),
unshielded
inside cabinets:
In separate bundles or cable
ducts (no minimum clearance
necessary)
outside cabinets:
On separate cable racks with a
clearance of at least 10 cm
•
Bus signals, shielded
(PROFIBUS)
•
Data signals, shielded
(programming devices,
operator panels, printers,
counter inputs, etc.)
•
Analog
signals,
shielded
•
DC voltage (
≤
60 V),
unshielded
•
Process
signals
(
≤
25 V),
shielded
•
AC voltage (
≤
25 V),
unshielded
•
Monitors (coaxial cable)
inside cabinets:
In separate bundles or cable
ducts (no minimum clearance
necessary)
outside cabinets:
On separate cable racks with a
clearance of at least 10 cm
DC and AC voltage (> 400 V),
unshielded
•
DC and AC voltage (> 400 V),
unshielded
In common bundles or cable
ducts
ETHERNET
In common bundles or cable
ducts
ETHERNET
Others
In separate bundles or cable
ducts with a clearance of at least
50 cm
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...