Commissioning
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
8-17
t
On
STOP-
LED
Off
3 s
max. 3 s
3 s
On
RUN-
LED
Off
1
2
3
Figure 8-9 Sequence of operation for cold start with the mode selector switch (CPU 318-2DP only)
What happens in the CPU during memory reset?
Table 8-5
Internal CPU events on memory reset
Event
CPU 313 / 314 / 314 IFM (314-5AE10) / 315 / 31x-2 DP /
CPU 31xC
CPU 312 IFM /
314 IFM (314-5AE0x)
1.
The CPU deletes the complete user program in main memory and RAM load
memory.
2.
The CPU deletes the retentive data.
3.
The CPU tests its own hardware.
CPU activities
4.
If a Memory Card or an MMC is inserted, the CPU
copies its runtime relevant data to main memory.
Tip: If the CPU cannot copy the data on Memory Card
or MMC and requests memory reset:
•
Remove the Memory Card or MMC
•
Resetting
CPU
memory
•
Read the diagnostic buffer.
The CPU copies
runtime relevant data
from EPROM memory
to main memory
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...