Testing functions, Diagnostics and Fault Elimination
S7-300 Programmable Controller Hardware and Installation
10-24
A5E00105492-01
Station Status 3
Table 10-15
Structure of Station Status 3 (Byte 2)
Bit
Description
0 to 6
0: These bits are always "0"
7
1:The DP slave is out of memory for received diagnostic messages.
The DP master cannot write all diagnostic messages sent by the DP slave to its diagnostic
buffer.
Master PROFIBUS address
The "Master-PROFIBUS address" diagnostic byte stores the DP address of the DP
master:
•
that has configured the DP slave and
•
has read and write access to the DP slave.
Table 10-16
Structure of the Master PROFIBUS address (byte 3)
Bit
Description
0 to 7
DP address of the DP master that has configured the DP slave and has read/write access to
that DP slave.
FFH: DP slave was not configured by a DP master
Manufacturer ID
The manufacturer ID contains a code specifying the DP slave's type.
Table 10-17
Structure of the manufacturer ID (byte 4 and 5)
Byte 4
Byte 5
Manufacturer ID for
80
H
2F
H
CPU 315-2-DP
80
H
6F
H
CPU 316-2-DP
80
H
7F
H
CPU 318-2
80
H
DO
H
313C-2-DP
80
H
D1
H
314C-2-DP
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...