Configuring
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
4-37
Longer cable lengths
If you want to implement cable lengths above those permitted in a segment, you
must use RS485 repeaters. The maximum cable length possible between two
RS485 repeaters corresponds to the cable length of a segment (see the following
Chapter). Please note that these maximum cable lengths only apply if no other
node is interconnected between the two RS485 repeaters. You can connect up to
nine RS485 repeaters in series.
Please note that you have to add the RS485 repeater when you determine the
number of nodes in your subnet, even if it is not assigned its own MPI/PROFIBUS
address.
Technical data and installation instructions are found ...
... in the RS485 Repeater product information.
PG patch cord
Table 4-20
PG patch cord
Type
Order No.
PG patch cord
6ES7 901-4BD00-0XA0
Stub cables
If you do not want to install the bus cable directly in the bus connector (for
example, when using an L2 bus terminal), you must take into account the
maximum length possible for the stub cable.
Up to 3 Mbps you can use a PROFIBUS cable with bus connector for your
connection.
Use the patch cord to connect the PG or PC when operating above 3 Mbps. In your
bus assembly you can use multiple PG patch cords with this order no. Do not use
other types of stub cables.
The maximum cable lengths for PG patch cords ...
... is found in the Chapter Cable lengths.
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...