S5-100U
Interrupt Processing
10.2
Calculating Interrupt Reaction Times
The total reaction time is is the sum of the following times:
•
Signal delay of the module triggering the interrupt (= time from the input signal change
triggering the interrupt to the activation of the interrupt line)
•
Interrupt reaction time of the CPU
•
Execution time of the interrupt program (= sum of all STEP 5 statements in the interrupt
evaluation program)
Calculate the interrupt reaction times as follows:
CPU’s interrupt reaction time = basic reaction time + additional reaction times
The basic reaction time is 0.6 ms and is valid if the following conditions exist:
•
No integrated FBs were used.
•
No parameters for the integral clock are set.
•
No programmer/OP functions are present.
•
OB13 has not been programmed.
•
No SINEC L1 is connected.
The additional reaction times are variable. They are listed in Table 10-1.
Table 10-1. Additional Reaction Times
Interrupt Reaction
Times
Additional Running Functions of the
Programmable Controller
Integrated FBs
Parameters set for clock
OP functions
Programmer functions:
Status block/Transfer block
Output address
Compress
• If no blocks are moved
• If blocks are moved
SINEC L1 bus to the programmer interface
0.5 ms
0.2 ms
Depending on the number of bytes used
for loading the memory
0.5 ms
18 ms per kbyte
•
Depending on the number of blocks
present (after overall reset 31 ms)
•
600 ms per each 1kword of
instructions in the block to be
moved
8.0 ms
EWA 4NEB 812 6120-02b
10-5
Summary of Contents for SIMATIC S5-100U
Page 6: ...EWA 4NEB 812 6120 02b ...
Page 16: ...EWA 4NEB 812 6120 02b ...
Page 21: ...1 The SIMATIC S5 System Family EWA 4NEB 812 6120 02b ...
Page 22: ...Figures 1 1 Members of the SIMATIC S5 System Family 1 1 EWA 4NEB 812 6120 02b ...
Page 23: ......
Page 27: ......
Page 36: ...EWA 4NEB 812 6120 02b ...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 102: ...EWA 4NEB 812 6120 02b ...
Page 156: ...EWA 4NEB 812 6120 02b ...
Page 232: ...EWA 4NEB 812 6120 02b ...
Page 268: ...EWA 4NEB 812 6120 02b ...
Page 272: ...EWA 4NEB 812 6120 02b ...
Page 336: ...EWA 4NEB 812 6120 02b ...
Page 352: ...EWA 4NEB 812 6120 02b ...
Page 412: ...EWA 4NEB 812 6120 02b ...
Page 482: ...EWA 4NEB 812 6120 02b ...
Page 484: ...EWA 4NEB 812 6120 02b ...
Page 505: ...B Dimension Drawings EWA 4NEB 812 6120 02b ...
Page 515: ...C Active and Passive Faults in Automation Equipment EWA 4NEB 812 6120 02b ...
Page 516: ...EWA 4NEB 812 6120 02b ...
Page 522: ...EWA 4NEB 812 6120 02b ...
Page 523: ...D Information for Ordering Accessories EWA 4NEB 812 6120 02b ...
Page 524: ...EWA 4NEB 812 6120 02b ...
Page 530: ...EWA 4NEB 812 6120 02b ...
Page 531: ...E Reference Materials EWA 4NEB 812 6120 02b ...
Page 532: ...EWA 4NEB 812 6120 02b ...
Page 534: ...EWA 4NEB 812 6120 02b ...
Page 535: ...F Siemens Addresses Worldwide EWA 4NEB 812 6120 02b ...
Page 536: ...EWA 4NEB 812 6120 02b ...
Page 542: ...EWA 4NEB 812 6120 02b ...
Page 543: ...Index EWA 4NEB 812 6120 02b ...
Page 544: ...EWA 4NEB 812 6120 02b ...
Page 550: ...EWA 4NEB 812 6120 02b ...