S5-100U
STEP 5 Operations
Block End “BE”
The “BE” operation terminates a block. Data blocks do not need to be terminated. “BE” is always
the last statement in a block.
In structured programming, program scanning jumps back to the block where the call for the current
block was made.
Boolean logic operations cannot be continued in a higher-order block.
Example:
Program block PB3 is terminated by the “BE” statement.
.
.
.
.
.
.
BE
STL
The “BE” statement terminates
program block PB3 and causes
program scanning to return to
organization block OB1.
Explanation
Program Sequence
BE
OB1
PB3
JU PB3
Unconditional Block End “BEU”
The “BEU” operation causes a return within a block. However, jump operations can bypass the
“BEU” operation in function blocks (see sections 8.2.10 and 8.3.4).
Binary logic operations cannot be continued in a higher-order block.
Example:
Scanning of function block FB21 is terminated regardless of the RLO.
.
.
.
.
JC=
BEU
.
.
.
.
BE
The “BEU” statement causes program
scanning to leave function block FB21
and return to program block PB8.
STL
Explanation
Program Sequence
PB8
FB21
JC=
BEU
BE
JU FB21
EWA 4NEB 812 6120-02b
8-37
Summary of Contents for SIMATIC S5-100U
Page 6: ...EWA 4NEB 812 6120 02b ...
Page 16: ...EWA 4NEB 812 6120 02b ...
Page 21: ...1 The SIMATIC S5 System Family EWA 4NEB 812 6120 02b ...
Page 22: ...Figures 1 1 Members of the SIMATIC S5 System Family 1 1 EWA 4NEB 812 6120 02b ...
Page 23: ......
Page 27: ......
Page 36: ...EWA 4NEB 812 6120 02b ...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 102: ...EWA 4NEB 812 6120 02b ...
Page 156: ...EWA 4NEB 812 6120 02b ...
Page 232: ...EWA 4NEB 812 6120 02b ...
Page 268: ...EWA 4NEB 812 6120 02b ...
Page 272: ...EWA 4NEB 812 6120 02b ...
Page 336: ...EWA 4NEB 812 6120 02b ...
Page 352: ...EWA 4NEB 812 6120 02b ...
Page 412: ...EWA 4NEB 812 6120 02b ...
Page 482: ...EWA 4NEB 812 6120 02b ...
Page 484: ...EWA 4NEB 812 6120 02b ...
Page 505: ...B Dimension Drawings EWA 4NEB 812 6120 02b ...
Page 515: ...C Active and Passive Faults in Automation Equipment EWA 4NEB 812 6120 02b ...
Page 516: ...EWA 4NEB 812 6120 02b ...
Page 522: ...EWA 4NEB 812 6120 02b ...
Page 523: ...D Information for Ordering Accessories EWA 4NEB 812 6120 02b ...
Page 524: ...EWA 4NEB 812 6120 02b ...
Page 530: ...EWA 4NEB 812 6120 02b ...
Page 531: ...E Reference Materials EWA 4NEB 812 6120 02b ...
Page 532: ...EWA 4NEB 812 6120 02b ...
Page 534: ...EWA 4NEB 812 6120 02b ...
Page 535: ...F Siemens Addresses Worldwide EWA 4NEB 812 6120 02b ...
Page 536: ...EWA 4NEB 812 6120 02b ...
Page 542: ...EWA 4NEB 812 6120 02b ...
Page 543: ...Index EWA 4NEB 812 6120 02b ...
Page 544: ...EWA 4NEB 812 6120 02b ...
Page 550: ...EWA 4NEB 812 6120 02b ...