S5-100U
Installation Guidelines
3.3.2
Electrical Configuration with External I/Os
Figures 3-18, 3-19, and 3-20 display different configuration possibilities. Pay attention to the
following points when you design your configuration. The numbers appearing in parentheses in the
following points refer to the numbers in Figures 3-18 to 3-20.
•
You must have a main switch (1) in accordance with VDE 0100 for your S5-100U, the sensors,
and the actuators.
•
You do not need an additional fuse (2) to connect your S5-100U and the load circuit to power if
your radial lines are a maximum of 3 meters (9.84 feet) long and are inherently earth-fault proof
and short-circuit proof.
•
You need a load power supply (3) for 24 V DC load circuits.
- You need a back-up capacitor (rating: 200
µ
F per 1 A of load current) if you have non-
stabilized load power supplies.
•
If you have AC load circuits, galvanic isolation via a transformer (4) is recommended.
•
You should ground the load circuit at one end.
Provide a removable connection (5) to the
ground conductor on the load power supply (terminal M) or on the isolating transformer.
- You must provide earth-fault monitoring for any non-grounded load circuits.
•
You must separately fuse (6 and 7) the load voltage for sensor circuits and for actuator circuits.
•
You must connect the standard mounting rail of the S5-100U to the ground conductor through a
capacitor (8, to suppress high-frequency noise) for a non-grounded configuration.
•
You must have a low-resistance connection between the standard mounting rail and the
cabinet’s chassis ground (10) for a grounded configuration.
•
You need a power fuse (9) to protect against a short-circuit occurring in the power supply.
EWA 4NEB 812 6120-02b
3-21
Summary of Contents for SIMATIC S5-100U
Page 6: ...EWA 4NEB 812 6120 02b ...
Page 16: ...EWA 4NEB 812 6120 02b ...
Page 21: ...1 The SIMATIC S5 System Family EWA 4NEB 812 6120 02b ...
Page 22: ...Figures 1 1 Members of the SIMATIC S5 System Family 1 1 EWA 4NEB 812 6120 02b ...
Page 23: ......
Page 27: ......
Page 36: ...EWA 4NEB 812 6120 02b ...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 102: ...EWA 4NEB 812 6120 02b ...
Page 156: ...EWA 4NEB 812 6120 02b ...
Page 232: ...EWA 4NEB 812 6120 02b ...
Page 268: ...EWA 4NEB 812 6120 02b ...
Page 272: ...EWA 4NEB 812 6120 02b ...
Page 336: ...EWA 4NEB 812 6120 02b ...
Page 352: ...EWA 4NEB 812 6120 02b ...
Page 412: ...EWA 4NEB 812 6120 02b ...
Page 482: ...EWA 4NEB 812 6120 02b ...
Page 484: ...EWA 4NEB 812 6120 02b ...
Page 505: ...B Dimension Drawings EWA 4NEB 812 6120 02b ...
Page 515: ...C Active and Passive Faults in Automation Equipment EWA 4NEB 812 6120 02b ...
Page 516: ...EWA 4NEB 812 6120 02b ...
Page 522: ...EWA 4NEB 812 6120 02b ...
Page 523: ...D Information for Ordering Accessories EWA 4NEB 812 6120 02b ...
Page 524: ...EWA 4NEB 812 6120 02b ...
Page 530: ...EWA 4NEB 812 6120 02b ...
Page 531: ...E Reference Materials EWA 4NEB 812 6120 02b ...
Page 532: ...EWA 4NEB 812 6120 02b ...
Page 534: ...EWA 4NEB 812 6120 02b ...
Page 535: ...F Siemens Addresses Worldwide EWA 4NEB 812 6120 02b ...
Page 536: ...EWA 4NEB 812 6120 02b ...
Page 542: ...EWA 4NEB 812 6120 02b ...
Page 543: ...Index EWA 4NEB 812 6120 02b ...
Page 544: ...EWA 4NEB 812 6120 02b ...
Page 550: ...EWA 4NEB 812 6120 02b ...