Service and maintenance
12.2 Error messages
SIMATIC RF650R/RF680R/RF685R
Configuration Manual, 03/2018, C79000-G8976-C386-06
293
"ER"
LED
XML/
LED
(hex)
PLC block
(hex)
Error description
2 Hz
0x54
0xE5FE04 Invalid data block number (DBN) on the reader/communications module
--
0x55
0xE5FE05 Invalid data block number (DBN) in the Ident profile
2 Hz
0x56
0xE5FE06 Invalid data block length (DBL) on the reader/communications module
--
0x57
0xE5FE07 Invalid data block length (DBL) in the Ident profile
2 Hz
0x58
0xE5FE08 The previous command is still active or the buffer is full.
A new command was sent to the reader or communications module although the last com-
mand is still active.
•
The active command can only be aborted with "INIT".
•
Before a new command can be started, "DONE bit = 1" must be set (exception: "INIT").
•
Two Ident profile calls had the same "HW_ID", "CM_CHANNEL" and "LADDR" parame-
ter settings.
•
Two Ident profile calls are using the same pointer.
•
After eliminating the error, an "INIT" must be executed.
•
When working with command repetition (e.g., fixed code transponder), no data is being
fetched from the transponder. The data buffer on the reader/communications module
has overflowed. Transponder data has been lost.
--
0x59
0xE5FE09 The reader/communications module runs a hardware reset ("INIT_ACTIVE" set to "1"). The
Ident profile expects an "INIT" (bit 15 in the cyclic control word).
--
0x5A 0xE5FE0A The "CMD" command code and the relevant acknowledgement do not match. This can be a
software error or synchronization error that cannot occur in normal operation.
--
0x5B 0xE5FE0B Incorrect sequence of acknowledgement frames (TDB / DBN)
--
0x5C 0xE5FE0C Synchronization error (incorrect increment of AC_H / AC_L and CC_H / CC_L in the cyclic
control word). "INIT" had to be executed.
--
--
0xE5FE81 Communications error between reader and communications module
Access denied
--
--
0xE5FE82 Communications error between reader and communications module
Resource is occupied
--
--
0xE5FE83 Communications error between reader and communications module
Functional error of the serial interface
--
--
0xE5FE84 Communications error between reader and communications module
Other faults/errors
2 Hz
0x61
0xE6FE01 Unknown command
An uninterpretable XML command was sent to the reader or the Ident profile sends an
uninterpretable command to the reader.
Possible causes:
•
The "AdvancedCmd" block was supplied with an incorrect "CMD".
•
The "CMD" input of the "AdvancedCmd" block was overwritten.
--
0x62
0xE6FE02 Invalid command index (CI)