Configuration parameters (CFG)
5.9 CFG11: Read mode - read data
RF290R
Configuration Manual, 09/2014, C79000-G8976-C377-01
33
Name
Description
Function
Description
COM-
PREFIX
In "Scan Mode" only
•
b0 no COM prefix is sent.
•
b1 the reader transfers the COM-ADR before every data set.
READ_-
COM-
PLETE_-
BANK
If this bit is set, the reader reads out all memory blocks from the selected memory bank.
•
b0 the reader reads out the memory blocks according to the settings in DB-ADR, DB-N, D-
Start and D-LGT.
•
b1 the reader reads out all blocks of the selected memory bank.
Note:
This functionality is restricted to memory banks with a maximum size of 255 bytes.
DB-ADR
Address of the first data block. Range: 0x00...0xFF.
1)
DB-N
Number of data blocks. Range: 0x01...0x20.
The data block size in "Buffered Read Mode" is always 4 bytes.
2)
EAS-
MODE
The EAS-MODE defines the settings for the automatic read modes.
Bit
7
6
5
4
3
2
1
0
Function
-
ALARM-
MODE
-
-
TAG-TYPE
Function
Description
ALARM-
MODE
•
b0 MODE 0 (The relay only becomes active if EAS was detected.)
•
b1 MODE 1 (The relay becomes active when EAS was detected and/or a UID was read.)
TAG-
TYPE
Defines which tag type is supported.
•
b0000 reserved
•
b0001 NXP
•
b0010 Fujitsu
D-START This parameter defines the first byte in the raw data (defined by DB-ADR and D-LGT) that is transferred in
"Scan Mode". To transfer the entire data block, D-START must be set to 0.
Note:
The size of a data block depends on the type of transponder.
D-LGT
D-LGT defines the length of the raw data transferred in "Scan Mode". Number of data bytes to be transferred
beginning with D-START.