Appendix
A.5 Error codes of the transponders
RF290R
Configuration Manual, 09/2014, C79000-G8976-C377-01
107
Hexadecimal
value
Buffer status
0x94
Other data:
•
More transponder data sets have been requested than the transponder pro-
tocol is capable of transferring simultaneously.
0x95
ISO 15693 error:
•
Additional error code for ISO 15693 transponder was sent with the response
data
A.5
Error codes of the transponders
Hexadecimal
value
Definition of the response error code
0x01
The command is not supported or is request code is not known.
0x02
The command is not recognized, Example: Format error occurred.
0x03
The option is not supported.
0x0F
Unknown error
0x10
The specified block is not available (does not exist).
0x11
The specified block is already locked and cannot be locked again.
0x12
The specified block is locked and its content cannot be changed.
0x13
The specified block was not programmed successfully.
0x14
The specified block was not saved successfully.
0xA0 ... 0xDF
Error codes of user-defined commands
All others
Reserved for future use
A.6
LED functions
When applying the power or resetting the reader, all four LEDs flash three times (LED test),
and the green "PWR" LED is then lit permanently:
LED
Color
Meaning
PWR
green
Power
Power is on.
ACT
yellow
Active
Communication on the interface (to the reader/host).