Protocols for controlling the reader
7.9 [0x72] Set Output
RF290R
Configuration Manual, 09/2014, C79000-G8976-C377-01
55
7.9
[0x72] Set Output
With the "Set Output" command, you can enable the outputs of the reader for a limited time
or an unlimited time.
Each output adopts the state defined by the OUTx-mode byte during the period specified in
the protocol (OUT-TIME). The flashing frequency is specified by the OUTx-frq byte. With this
protocol, the outputs can be turned on or off for the specified time. If the reader receives a
"Set Output" command, all the times active up to now are overwritten by the new times in the
protocol provided they are > 0.
Table 7- 19
Host → reader
Byte
1
2
3
4
5
6
7
8
9
10, 11 n -1 ... n
Content
STX
MSB
ALENG
TH
LSB
ALENG
TH
COM-
ADR
[0x72]
[0x01]
[0x01]
0x81
OUT-S
OUT-
TIME
CRC16
Default
0x02
-
-
-
-
-
-
-
-
-
-
Table 7- 20
Reader → host
Byte
1
2
3
4
5
6
7, 8
Content
STX
MSB
ALENGTH
LSB
ALENGTH
COM-ADR
[0x72]
STATUS
1)
CRC16
Default
0x02
-
-
-
-
-
-
1)
You will find further information in the Appendix (Page 103).
Name
Description
OUT-S
OUT-S (Output State) defines the state of the output during the time defined by OUT-TIME.
Bit
7
6
5
4
3
2
1
0
Function
-
-
-
-
-
-
-
OUT
mode
Function
Description
OUT
mode
•
b01 ON: Output while OUT-TIME = active
•
b10 OFF: Output while OUT-TIME = inactive
OUT-
TIME
Using the values defined by OUT-TIME, the outputs can be activated for a restricted or unrestricted time. The
time values 0 and 65535 (0xFFFF) are exceptions to this.
0x0001
1 x
100 ms
→ 100
ms
...
...
→
...
0xFFFE
65534 x
100 ms
→
1:49:13 h
0xFFFF
permanently active