Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
A-16
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
Number Effect/cause Remedy
190100 The area pointer is not updated because the
configured address for this area pointer is not
available.
Type
1 Warning alarms
2 Error alarms
3 PLC acknowledgment
4 HMI device acknowledgment
5 LED mapping
6 Trend request
7 Trend transfer 1
8 Trend transfer 2
No.:
is the consecutive number displayed in WinCC
flexible ES.
Check the configuration.
190101 The area pointer is not updated because it is not
possible to map the PLC type in the area pointer
type.
Parameter type and no.:
see alarm 190100
-
190102 The area pointer is updated following an error
status after the cause of the last error state has
been eliminated (return to normal operation).
Parameter type and no.: See alarm 190100.
-
200000 Coordination is not executed because the address
configured in the PLC does not exist/has not been
set up.
Change the address or set up the address in the PLC.
200001 Coordination is not executed because the address
configured in the PLC does not exist/has not been
written.
Change the address or set up the address in the PLC in
an area which can be written to.
200002 Coordination is currently not being performed
because the address format of the area pointer
does not match the internal storage format.
Internal error
200003 Coordination can be executed again because the
last error status has been eliminated (return to
normal operation).
-
200004 The coordination may not be executed.
-
200005 No additional data is read or written. Possible
causes:
•
The cable is defective.
•
The PLC does not respond, is defective, etc.
•
The system is overloaded.
Check that the cable is plugged in and the PLC is
operational.
Reboot the system if the system alarm is displayed
continuously.
200100 Coordination is not executed because the address
configured in the PLC does not exist/has not been
set up.
Change the address or set up the address in the PLC.
200101 Coordination is not executed because the address
configured in the PLC does not exist/has not been
written.
Change the address or set up the address in the PLC in
an area which can be written to.
200102 Coordination is currently not being performed
because the address format of the area pointer
does not match the internal storage format.
Internal error