Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
A-4
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
System alarm parameters
The system alarms may contain parameters which are coded but which are relevant with
respect to the cause of an error. They provide a reference to the source code from the
runtime software. These parameters are issued after the text "Error code:".
System alarm parameters
Number Effect/cause Remedy
10000 The print job cannot be started or was
!
e-establ
due to an unknown cause. The printer is not
configured correctly. Or There are no rights for a
network printer.
A power failure occurred during data transfer.
Check the printer settings, cable connections and power
supply.
Setup the printer again. Request rights for the network
printer.
If an error occurs repeatedly, contact the hotline.
10001 No printer is installed or a default printer has not
been selected.
Install a printer and/or select it as the default printer.
10002 The graphics buffer for printing is full. Up to two
graphics are buffered.
Wait before triggering print jobs.
10003 Graphics can be buffered again.
-
10004 The buffer for printing lines in text mode (e.g.
alarms) is full. Up to 1000 lines are buffered.
Wait before triggering print jobs.
10005 Text lines can be buffered again.
-
10006 The Windows printing system reports an error.
Refer to the printed text and the error number to
determine the possible causes. Nothing is printed
or the printout is incorrect.
Repeat the action if necessary.
20010 An error has occurred in the specified script line.
The execution of the script was therefore aborted.
Note the system alarms that may have occurred
prior to this.
Select the specified script line in the configuration.
Ensure that the tags used are the allowed types. Check
system functions for the correct number and types of
parameters.
20011 An error has occurred in a script that was called by
the specified script.
The execution of the script was therefore aborted in
the called script.
Note the system alarms that may have occurred
prior to this.
In the configuration select the script that has been called
directly or indirectly by the specified script.
Ensure that the tags used are the allowed types.
Check system functions for the correct number and types
of parameters.
20012 The configuration data is inconsistent. The script
could therefore not be generated.
Recompile the configuration.
20013 The script components from WinCC flexible runtime
are not correctly installed. Therefore, no scripts can
be executed.
Reinstall WinCC flexible runtime.
20014 The system function returns a value that is not
written in any return tag.
Select the specified script in the configuration.
Check whether the script name has been assigned a
value.
20015 Too many scripts have been triggered in quick
succession. When more than 20 scripts are queued
for processing, any subsequent scripts are rejected.
In this case, the script indicated in the alarm is not
executed.
Find what is triggering the scripts. Extend the times, e.g.
the polling time of the tags which trigger the scripts.
30010 The tag could not accept the function result, e.g.
when it has exceeded the value range.
Check the tag type of the system function parameter.