Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
A-12
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
Number Effect/cause Remedy
140006 No tag updating or writing is executed because the
baud rate is incorrect.
Select a different baud rate in WinCC flexible (according
to module, profile, communication peer, etc.).
140007 Tags are not updated or written because the bus
profile is incorrect (see %1).
The following parameters cannot be entered in the
registry:
1: Tslot
2: Tqui
3: Tset
4: MinTsdr
5: MaxTsdr
6: Trdy
7: Tid1
8: Tid2
9: Gap Factor
10: Retry Limit
Check the user-defined bus profile.
Check the connection and whether the PLC is switched
on.
Check the parameter definitions in the Control Panel
using "Set PU/PC interface".
Restart the system.
140008 No tag updating or writing is executed because
baud rate is incorrect. The following parameters
cannot be entered in the registry:
0: General error
1: Incorrect version
2: Profile cannot be entered in the registry.
3: Subnet type cannot be entered in the registry.
4: Target rotation time cannot be entered in the
registry.
5: Highest address (HAS) incorrect.
Check the connection and whether the PLC is switched
on.
Check the parameter definitions in the Control Panel
using "Set PU/PC interface".
Restart the system.
140009 No tag updating or writing is executed because the
module for the S7 communication was not found.
Reinstall the module in the Control Panel using "Set
PU/PC interface".
140010 No S7 communication peer could be found
because the PLC is switched off.
DP/T:
The option
“
Is not active as the only master
”
is set
in the Control Panel under
“
Set PU/PC interface
”
.
Switch the PLC on.
DP/T:
If only one master is connected to the network, deactivate
the option "Is not active as the only master" in "Set
PU/PC interface".
If there is more than one master connected to the
network, activate them. Do not change any settings
otherwise the bus will be disrupted.
140011 No tag updating or writing is executed because the
communication is interrupted.
Check the connection and that the communication peer is
switched on.
140012 There is an initialization problem (e.g. when WinCC
flexible Runtime has been closed in the Task
Manager).
or:
another application (e.g. STEP7) is active with
different bus parameters and the driver cannot be
started with the new bus parameters (e.g. baud
rate).
Restart the HMI device.
or:
Start WinCC flexible Runtime first and then the other
applications.
140013 The MPI cable is not plugged in; there is no power
supply.
Check the connections.
140014 "Configured bus address already assigned."
Modify the HMI device address in the configuration in
PLC.