Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
A-10
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
Number Effect/cause Remedy
80033 "System Defined" is selected in the data log as the
data source name. This results in an error. No
logging is made to the database log whereas the
logging to the CSV logs works.
Install MSDE again.
80034 An error has occurred in the initialization of the
logs. An attempt has been made to create tables as
a backup. This did not work. A backup has been
made of the tables of the corrupt log and the log
has been newly started (empty).
No action is necessary. However, it is recommended to
save the backups or delete them to free up memory.
80035 An error has occurred in the initialization of the
logs. An attempt has been made to create backups
of the tables and this has failed. No logging or
backup has been performed.
It is recommended to save the backups or delete them to
free up memory.
110000 The operating mode has been changed. The
operating mode is now 'offline'.
-
110001 The operating mode has been changed. The
operating mode is now "online".
-
110002 The operating mode cannot be changed.
Check the connection to the PLCs.
Check whether the address area for the area pointer 88
“
Coordination" in the PLC is available.
110003 The operating mode of the specified controller has
been changed by the system function
"SetConnectionMode".
The operating mode is now "offline".
-
110004 The operating mode of the specified controller has
been changed by the system function
"SetConnectionMode".
The operating mode is now "online".
-
110005 An attempt was made to use the system function
"SetConnectionMode" to switch the specified PLC
to the "online" operating mode although the entire
system is in the "offline" mode. This switchover is
not permissible. The PLC remains in operating
mode "offline".
Switch the complete system to operating mode "online"
and execute the system function again.
110006 The content of the area pointer "User version" does
not match the user version configured WinCC
flexible. WinCC flexible Runtime is therefore
closed.
Check:
•
The user version entered on the controller
•
The user version entered in WinCC flexible
120000 The trend is not displayed because an incorrect
axis to the trend or incorrect trend has been
configured.
Change the configuration.
120001 The trend is not displayed because an incorrect
axis to the trend or incorrect trend has been
configured.
Change the configuration.
120002 The trend is not displayed because the tag
assigned tries to access an invalid PLC address.
Check if the data area for the tag exists in the PLC, the
configured address is correct and the value range for the
tag is correct.
130000 The action was not executed.
Close the other programs.
Delete files no longer required from the hard disk.
130001 The action was not executed.
Delete files no longer required from the hard disk.