Operating recipes
10.6 Recipe data record administration
TP 270, OP 270, MP 270B (WinCC flexible)
10-16
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
4. Enter the values for the recipe data records.
The configuration data may already contain default values for the recipe data record.
5. Use the "Save" button in the recipe view or the corresponding button on the HMI device
that is configured with this function.
Result
The new recipe data records will be saved to the selected recipe. If the recipe data records
already exists, a system alarm will be output to the screen.
Copying a recipe data record
You copy a recipe record by saving it under a new name.
1. Select the recipe on the HMI device in which you want to edit an existing recipe data
record.
2. Select the recipe data record that you want to edit on the HMI device.
3. Assign a new name to the recipe data record.
As soon as you close the "Recipe data record" input field, the next free recipe data record
number will be automatically assigned to the recipe data record. You may change the
recipe data record number.
4. Use the "Save" button in the recipe view or the corresponding button on the HMI device
that is configured with this function.
Result
The recipe data record is stored under the new name.
Modify recipe record
1. Select the recipe on the HMI device in which you want to edit an existing recipe data
record.
2. Select the recipe data record that you want to edit on the HMI device.
3. Replace the old values with new ones.
4. Use the "Save" button in the recipe view or the corresponding button on the HMI device
that is configured with this function.
Result
The modified values are applied to the recipe data record.