Installing the S7-400
2-24
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
4. Attach the dummy plates to the free slots:
– Place the dummy plates on the rear wall of the cable routing,
– Push the dummy plates back so that the noses of the dummy plates will fit
into the cutouts provided,
– Push the dummy plates in until the snap-in mechanism engages in the
openings on the back of the cable routing.
5. Then install the fan assembly in the 19-inch pitch directly under the rack or
between two racks. Use M6 size screws for mounting.
The following figure shows how to mount the fan subassembly between two
racks.
9 10 11 12 13 14 15 16 17 18
9 10 11 12 13 14 15 16 17 18
Blanking
cover
19-inch
reference level
6. Refit the left cover.
7. Secure the left cover with the quick-release lock.
Monitoring the Fan Subassembly
To monitor the functioning of the fan subassembly via your program, connect the
outputs to a digital module.
Further details on the monitoring concept can be found in the Reference Manual,
Chapter 9.