Networking
5-5
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Communication from PG/OP to Module without MPI
If one of the programming devices or operator panels connected to a multipoint
interface (MPI) communicates with an S7-400 module which does not have an
MPI connection (for example, SIMATIC NET CPs, FM 456 etc.), this module can be
reached via the CPU to whose MPI the programming device or operator panel is
connected. In this case, the CPU simply acts as an intermediary for the transfer.
This type of connection between a programming device or operator panel and a
module only communicating via the communication bus occupies two connection
resources in the CPU.
CPU
CP or FM
MPI
C bus
PG or OP
Two connection resources
occupied in the CPU
S7-400
station
One connection
resource occupied
One connection
resource occupied
Figure 5-1
Communication between Programming Device/Operator Panel and a Module
without MPI
Maximum Number of Connections via MPI
When configuring the connections of a CPU 416 via MPI, remember to include the
PG connection in the maximum number of possible connections.