Networking
5-28
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Table 5-4
Features of the Fiber-Optic Cables, continued
Description
SIMATIC NET PROFIBUS
Plastic Fiber-Optic
Duplex Conductor
Plastic Fiber-Optic
Standard Cable
PCF Fiber-Optic
Standard Cable
Resistance to lateral pressure
per 10 cm cable length
(short-term)
35 N/ 10 cm
100 N/ 10 cm
750 N/ 10 cm
Bend radii
•
Single bend
(without tensile force)
•
Multiple bends
(with tensile force)
30 mm
50 mm
(flat side only)
100 mm
150 mm
75 mm
75 mm
Permissible environmental
conditions
•
Transport/storage
temperature
•
Laying temperature
•
Operating temperature
-30
_
C to +70
C
0
C to +50
C
-30
C to +70
C
-30
C to +70
C
0
C to +50
C
-30
C to +70
C
-30
C to +70
C
-5
C to +50
C
-20
C to +70
C
Resistance against
•
Mineral oil ASTM no. 2,
grease or water
•
UV radiation
Conditional
1
)
Not UV-resistant
Conditional
1
)
Conditional
1)
Conditional
1
)
Conditional
1
)
Flame retardance
Flame retardant in accordance with the VW-1 flame test to UL 1581
External dimensions
2.2 4.4 mm
0.01 mm
Diameter:
7.8
0.3 mm
Diameter:
4.7
0.3 mm
Weight
7.8 kg/km
65 kg/km
22 kg/km
1
Please ask your Siemens contact about specific applications.