Assembling and Installing Systems
A-18
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Table A-2
Cabling Inside Buildings, continued
Run ...
and Cables for ...
Connect Cables for ...
DC voltage
(
60 V and
400 V), unshielded
AC voltage
(
25 V and
400 V), unshielded
LAN signals, shielded
(SINEC L1, PROFIBUS DP)
Data signals, shielded
(programming devices, operator
panels, printers, counter inputs,
etc.)
Analog signals, shielded
DC voltage
(
60 V), unshielded
Process signals
(
25 V), shielded
AC voltage
(
25 V), unshielded
Monitors (coaxial cable)
in separate bundles or cable
ducts (no minimum clearance
necessary)
DC voltage
(
60 V and
400 V), unshielded
AC voltage
(
25 V and
400 V), unshielded
in common bundles or cable
ducts
DC and AC voltages
(
400 V), unshielded
Inside cabinets:
in separate bundles or cable
ducts (no minimum clearance
necessary)
Outside cabinets:
on separate cable racks with a
clearance of at least 10 cm (3.93
in.)
DC and AC voltages
(
400 V), unshielded
LAN signals, shielded
(SINEC L1, PROFIBUS DP)
Data signals, shielded
(programming devices, operator
panels, printers, counter inputs,
etc.)
Analog signals, shielded
DC voltage
(
60 V), unshielded
Process signals
(
25 V), shielded
AC voltage
(
25 V), unshielded
Monitors (coaxial cable)
Inside cabinets:
in separate bundles or cable
ducts (no minimum clearance
necessary)
Outside cabinets:
on separate cable racks with a
clearance of at least 10 cm (3.93
in.)
DC voltage
(
60 V and
400 V), unshielded
AC voltage
(
25 V and
400 V), unshielded
DC and AC voltages
(
400 V), unshielded
DC and AC voltages
(
400 V), unshielded
in common bundles or cable
ducts
ETHERNET
ETHERNET
in common bundles or cable
ducts
Others
in separate bundles or cable
ducts with a clearance of at least
50 cm (19.65 in.)