Wiring the S7-400
4-16
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
4.10
Interference-Free Configuration for Local and Remote
Connections
Use only Approved Components
Note
If you use components which are not approved for setting up local and remote
connections, interference rejection may be impaired.
Interference-Free Configuration for Local Connections
If you connect the CR and ER via suitable interface modules (send IM and receive
IM), no particular shielding and grounding need be implemented. Ensure, however,
that
•
All racks have a low-impedance connection to each other
•
The racks in a grounded arrangement have a star grounding configuration
•
The contact springs of the racks are clean and not bent and will therefore
ensure the discharge of interference currents.